The MSR μGard®2 MC2 chlorine gas detector (4-20 mA / 2-10 V transmitter) monitors chlorine continuously in water treatment plants, swimming pools and chlorination rooms. Its electrochemical sensor measures from 0-10 up to 0-20 ppm. It sends a linear 4-20 mA or 2-10 V signal to a gas controller, BMS or PLC.
Why choose the MC2 chlorine gas detector
- Calibration data is stored in the sensor head. A pre-calibrated head can be swapped on site, without bringing test gas to site.
- Digital signal processing with temperature compensation gives stable readings.
- 3-wire, 24 V DC, protected against reverse polarity and short circuits.
- Choose a sensor head only, a compact D housing, or an IP65 A housing. The A housing is also available with a display and 2 open-collector outputs for a horn and warning lamp.
- Works with PolyGard®2 controllers and sensor boards.
Chlorine gas detector specifications
| Gas | Chlorine (Cl2) |
| Measuring ranges | 0-10 or 0-20 ppm |
| Sensor | Electrochemical |
| Output | 4-20 mA or 2-10 V, 3-wire |
| Supply | 24 V DC |
| Housing options | Sensor head only; type D (94 x 65 x 57 mm); type A (94 x 130 x 57 mm, IP65), also with display |
| Operating temperature | -30 to +50 °C |
| Expected sensor life | > 2 years |
| Calibration interval | 6 months |
| Mounting height | 0.3-0.5 m above the floor (chlorine is heavier than air) |
Calibration and service
Gas Alarm calibrates and services MSR gas detectors through its service teams in NSW, SA and VIC. We recommend calibrating every 6 months, or sooner after a gas leak or high exposure.
Ordering
Part numbers start with MC2-0 (sensor head only), MC2-D (D housing) or MC2-A (A housing). Tell us the measuring range, housing and output you need, and we’ll quote the exact part number.