The MSR μGard®2 MC2 C2H4 gas detector (4-20 mA / 2-10 V transmitter) monitors ethylene continuously in fruit ripening rooms and cool stores. Its semiconductor sensor measures 20-2000 ppm. It sends a linear 4-20 mA or 2-10 V signal to a gas controller, BMS or PLC.
Why choose the MC2 C2H4 gas detector
- Calibration data is stored in the sensor head. A pre-calibrated head can be swapped on site, without bringing test gas to site.
- Digital signal processing with temperature compensation gives stable readings.
- 3-wire, 24 V DC, protected against reverse polarity and short circuits.
- Choose a sensor head only, a compact D housing, or an IP65 A housing. The A housing is also available with a display and 2 open-collector outputs for a horn and warning lamp.
- Works with PolyGard®2 controllers and sensor boards.
C2H4 gas detector specifications
| Gas | Ethylene (C2H4) |
| Measuring ranges | 20-2000 ppm |
| Sensor | Semiconductor |
| Output | 4-20 mA or 2-10 V, 3-wire |
| Supply | 24 V DC |
| Housing options | Sensor head only; type D (94 x 65 x 57 mm); type A (94 x 130 x 57 mm, IP65), also with display |
| Operating temperature | -30 to +60 °C |
| Expected sensor life | more than 5 years |
| Calibration interval | 12 months |
| Mounting height | 1.2-1.8 m (ethylene is about as heavy as air, so mount at breathing height) |
Calibration and service
Gas Alarm calibrates and services MSR gas detectors through its service teams in NSW, SA and VIC. We recommend calibrating every 12 months, or sooner after a gas leak or high exposure.
Ordering
Part numbers start with MC2-0 (sensor head only), MC2-D (D housing) or MC2-A (A housing). Tell us the measuring range, housing and output you need, and we’ll quote the exact part number.