The MSR μGard®2 MC2 R454C gas detector (4-20 mA / 2-10 V transmitter) monitors R454C continuously in refrigeration plant rooms, chillers, cold rooms and VRF/VRV air-conditioning systems. Its semiconductor sensor measures 20-2000 ppm. It sends a linear 4-20 mA or 2-10 V signal to a gas controller, BMS or PLC. The signal can start ventilation and raise an alarm when refrigerant leaks, which protects people and reduces refrigerant loss.

Why choose the MC2 R454C gas detector

  • Calibration data is stored in the sensor head. A pre-calibrated head can be swapped on site, without bringing test gas to site.
  • Digital signal processing with temperature compensation gives stable readings.
  • 3-wire, 24 V DC, protected against reverse polarity and short circuits.
  • Choose a sensor head only, a compact D housing, or an IP65 A housing. The A housing is also available with a display and 2 open-collector outputs for a horn and warning lamp.
  • Works with PolyGard®2 controllers and sensor boards.

R454C gas detector specifications

Gas Refrigerant R454C (FR03 group)
Measuring ranges 20-2000 ppm
Sensor Semiconductor
Output 4-20 mA or 2-10 V, 3-wire
Supply 24 V DC
Housing options Sensor head only; type D (94 x 65 x 57 mm); type A (94 x 130 x 57 mm, IP65), also with display
Operating temperature -30 to +60 °C
Expected sensor life more than 5 years
Calibration interval 12 months
Mounting height 0.3-0.5 m above the floor (R454C is heavier than air)

Calibration and service

Gas Alarm calibrates and services MSR gas detectors through its service teams in NSW, SA and VIC. We recommend calibrating every 12 months, or sooner after a gas leak or high exposure.

Ordering

Part numbers start with MC2-0 (sensor head only), MC2-D (D housing) or MC2-A (A housing). Tell us the measuring range, housing and output you need, and we’ll quote the exact part number.