The MSR μGard®2 MC2 R1234yf LFL gas detector monitors the refrigerant R1234yf in the ambient air and provides a linear 4–20 mA (or 2–10 V) output signal.

Semiconductor sensor head including digital value processing and self-control for the continuous monitoring of the ambient air to detect low-flammable refrigerants in the combustible range. The intelligent MC sensor head for detection of low-flammable refrigerant gases includes a semiconductor sensor element (Metal-Oxide Semiconductor – MOS) and electronics with a measuring amplifier and a µController as well as a module with a terminal for the analog output and the external power supply. The µProcessor converts the sensor heads measuring signal into a linear 4–20 mA signal (or 2–10 V). All relevant data and measured values of the sensor head are stored fail-safe in the internal memory of the µProcessor. The measured value display of the sensor heads is in % LEL (in this case, the unit “% LFL”, which is customary in this trade, is synonymous with LEL). The maintenance of the device can be done either by simply exchanging the sensor head or by using the comfortable, integrated calibration routine directly at the system.

The PolyGard® sensor head MC is used for the detection of low-flammable gases of the refrigerant class A2L when an analog 4–20 mA (or 2–10 V) signal is required.

Features of the MC2 R1234yf LFL gas detector

  • Internal functional control with integrated watchdog
  • Easy maintenance and calibration by exchange of the sensor head or by comfortable on-site calibration
  • Low zero-point drift
  • Sensor head with long life expectancy
  • Hardware and software according to SIL compliant development process
  • 4–20 mA (or 2–10 V) analog output with selectable signal output for Special Mode (fault, maintenance, service etc.)
  • Reverse polarity protected, overload and short-circuit proof
  • IP65 protection (when installed)

R1234yf LFL gas detector specifications

Gas R1234yf
Measuring range 0–50 % LEL (% LFL) (S2020-04-A)
Sensor Semiconductor (Metal-Oxide Semiconductor – MOS)
Power supply 18–29 V DC, reverse-polarity protected
Output 4–20 mA or 2–10 V, proportional, overload and short-circuit proof
Housing options Sensor head only (0); plastic housing type D, 94 x 65 x 57 mm; plastic housing type A, 94 x 130 x 57 mm, IP65 (type A also available with display, or with display and 2 open-collector outputs for horn and warning lamp)
Temperature range -30 / +60 °C
Humidity range 15–90 % RH, non-condensing
Life time in air > 5 years
Calibration interval 12 months
Relative gas density (air = 1) 4.00
Mounting height Mounting 0.3–0.5 m above the floor

Ordering

Order code: MC2-X-S2020-0X-A-X-P (housing, sensor element and measuring range, display, sensor housing P). Example: MC2-A-S2020-04-A-0-P = R1234yf sensor head, 0–50 % LEL, in plastic housing type A without display.

Datasheet (PDF)